The ERMETIQ ER-REH34 balancing valve with measuring scale (3/4", DN20) precisely regulates the flow rate of the medium supplying the system terminals. Correct balancing of hydraulic circuits keeps the system operating under design conditions, providing enhanced thermal comfort and low energy consumption. Valves from 1/2" to 2" are equipped with a Venturi flow-measurement device integrated into the valve body: the flow rate depends only on the Δp measured across the fixed Venturi orifice, giving a stable pressure signal, high accuracy, flexible installation without long downstream straight pipe sections and quiet operation. The Memory Stop function locks the setting, so the valve can be closed and reopened exactly to the previously balanced position. Brass body, EPDM hydraulic seals, PTFE obturator seal and polyamide handwheel; working medium water or water-glycol mixture (max. 50%); max. working pressure 16 bar; working temperature -20-120 °C; accuracy ±10%; 5 adjustment turns; 1/4" F pressure test ports. Kvs (fully open): 5.70. Installation and maintenance may only be carried out by qualified personnel.
Technical specifications
Valve body: brass
Hydraulic seals: EPDM
Obturator seal: PTFE
Handwheel: polyamide
Working medium: water or water-glycol mixture (max. 50%)
Max. working pressure: 16 bar
Working temperature range: -20-120 °C
Accuracy: ±10%
Number of adjustment turns: 5
Pressure test ports: 1/4" F (internal thread)
Size: 3/4" (DN20)
Kvs (fully open): 5.70
Ku values vs. handwheel turns (3/4", DN20)
Ku value: water flow in m3/h at 1 bar pressure drop.
0.5 turn: 0.51
1 turn: 0.76
2 turns: 1.80
3 turns: 3.24
4 turns: 3.98
Kvs (fully open): 5.70
Kvs: maximum flow capacity of the valve when fully open.
Installation and commissioning
Install or dismantle only when the system is cold and not under pressure; follow the arrow on the valve body. To ensure accuracy, provide a straight pipe section upstream: at least 5 pipe diameters after a bend/fitting, at least 10 diameters if the nearest upstream device is a pump. The handle has two scales: black numbers (0-4) show full 360° turns, red numbers (0-9) show 1/10 turn increments; "0-0" is fully closed and "5-0" (or 6.10) is fully open. For flow measurement connect the differential pressure gauge to the test ports (4) with the dedicated connectors (5), red high-pressure (+) probe to the inlet and blue low-pressure (-) probe to the outlet, read Δp, then determine the flow rate from the "Δp - Flow Rate" Venturi diagram in the data sheet for this valve size. Memory Stop: after balancing insert a 2.5 mm Allen key into hole (7) and turn counter-clockwise until the red indicator (3) is visible and level with the handle profile ("I" = Memory Stop ON, "O" = OFF). The valve is designed to be maintenance-free. Fit the insulation with the supplied Velcro; for chilled water seal with suitable mastic.
Operating principle – animation